Insulation monitoring device for de-energised loads
Application in TN, TT or IT systems
According to IEC 61557-8
Two separately configurable response values
Multi-functional LC display
The offline monitor of the IR420-D6 series is designed to monitor the insulation resistance of loads in the de-energized state. These loads, usually temporarily operated or de-energized most of the time, e.g. fire extinguisher pumps, slide valve drives etc are supplied from TN, TT or IT systems. During the shut-down periods, hohwever, humidity or other effects may cause insulation faults in the wiring or the loads which may go undetected. Switching the device on may then lead to the tripping of the protective device or may even result in motor fires and the device cannot be operated. In combination with a coupling device, the Isometers can also be used for higher voltages.
Insulation monitoring for de-energised TN, TT and unearthed systems AC, 3(N)AC and DC
Nominal voltage extendable via coupling device
Two separately adjustable response values 100 kΩ…10 MΩ
LEDs: Power On LED, LEDs Alarm 1, Alarm 2 for signalling insulation faults
Combined test/reset button
Two separate alarm relays with one changeover contact each
Fault memory behaviour, selectable
Push-wire terminal (two terminals per connection)