The MCL can be configured to user requirements for optimal integration with research equipment and protocols, creating a cost effective and safe working environment. The MCL includes partitioning and associated air cascading. Quality furniture and fittings finish the installation off, configured to end-user requirements.
Each MCL is supplied with a dedicated utilities chamber, securely housing mechanical and control equipment. All units undergo factory Acceptance testing before release for shipping.
Configuration:
Foyer, Vestibule and Containment laboratory (BSL-3) over 28 m².
Lockable utilities chamber.
Air pressure:
Foyer: +5Pa (±5Pa).
Vestibule: -15Pa (±5Pa).
BSL-3 laboratory: -35Pa (±5Pa).
Cascaded to minimum of 12 air changes per hour.
Air pressure safety systems:
Automatic control against filter loading.
Audible and visual alarming when out of range.
Ball-in –tube indicator of air flow direction.
Air quality:
Once-through non-recirculating.
Supply air: Primary and secondary filtration to 95% efficiency.
Exhaust air: HEPA filtration with final efficiency of 99,97%.
Advanced option:
Supply air HEPA filtration with final efficiency of 99,97%.
Controlled at 24°C (~2°C).
Key lock.
Electronic door interlock.
Emergency escape override.
Fire alarm.
Emergency exit.
Advanced option:
Biometrical access control.
Walk-in shower.
Pass-through hatch.
Decontamination systems -
Automated air decontamination programme with actuated low leakage dampers.