• Précisé knife edge positioning into the gel gasket for an easy leak prcof installation
• No needs of screwdrivers to rotate the fasteners, to avoid any nsk of filter damage during the installation
• Hinged front panel diffuser to allow access to the filter and to the test ports, wrthout removing it. allowing so a single person to carry out the maintenance opérations
Ease of testing
• No need of injecting huge quantity of emery otl in the ductwork or in the air handling unit. Only a small quantity of aérosol has to be injected directly into a single housing
• Ail the components for GMP tests are accessible from the room side
• One single person can carry out the leak test
• It is possible to check the pressure drop of the single HEPA/ULPA filter from the room side even if the second Ap port i9 permanently connected to a remote control System
Ease of maintenance
• Quick and easy opening of the hinged front panel to access to the housing
• Filters are replaced directfy from the room side
• Strong stainless steel structure with smooth surfaces, easily dean- able
Reliability
• Continuous welding to avotd leakage through the housing
• Reverse liquid seal gasket coupled with stainless steel knite edge, without risk of leakage or air by-pass from upstream the filter to the room
100% in-house housing leakage test class D according to EN 1507
HEPA/ULPA filters manufactured, tested and packaged in clean room, according to the EN 1822 Standard