Cylinder manifolds are an important element of gas management in hospitals. They ensure the supply with medical gases and control the gas pressure. The core of the system is the Gas Control Station.
The manifold control system shall conform to ISO 7396-1 – Medical gas pipeline systems, NHS Health Technical Memorandum HTM 2022 and HTM 02-01. The manifold control system shall provide an uninterrupted supply of a specific medical gas from equally sized high pressure cylinder banks via a suitable arrangement of pressure regulators, providing a constant downstream nominal pipeline gauge pressure of 400 kPa or 700 kPa. The entire system shall be ‘duplexed’ such that any single functional component failure will not affect the integrity of the medical gas supply. The manifold shall be supplied fully assembled and tested.
Automatic Manifolds provide a continuous supply of gas from two banks of cylinders by automatically changing to the standby bank when the duty bank has become depleted.
Manifolds are available for Oxygen, Nitrous Oxide, Entonox, Carbondioxide and Medical Compressed Air.
These manifolds comprise an automatic changeover panel with alarm & status monitoring, an isolation & relief valve assy, non-return valve, two group manifold headers, two group cylinder racks and tailpipes with gas specific cylinder connectors
FEATURES
10″ Touch-Screen Display
Colorful and easy-to-use display.
Manual and automatic adjustable working system.
Audio-visual status display and system failure display.
Remote access with Modbus-RTU and connection to Hospital BMS.
The pressure values of the changeovers for the cylinder banks groups can be adjusted both to right or left bank.